It’s suitable for B,C,D grade lighting-proof, This series surge protective device according to GB188021.1-2002, installed on the joint of LPZ1 or LPZ2 and LPZ3,usually installed in household distribution boards,computer equipment, information equipment,electronic equipment and in the socket box in front of control equipment or near the control equipment.
chical Parameters |
ANT1-8,2-,8,3-20 |
ANT1-15,2-15,3-20 |
ANT1-60 |
|||
Rated Operating Voltage Uc(V~) |
220V |
380V |
220V |
380V |
220V |
380V |
Maximum Continuous Operating Voltage Uc(V~) |
275V |
440V |
275V |
440V |
275V |
440V |
320V |
385V |
|||||
385V | ||||||
Voltage Protection Level Up(V~)KV |
≤0.8 |
≤1.0 |
≤1.0 |
≤1.8 |
≤1.2 |
≤2.4 |
≤1.4 |
≤2.0 |
|||||
≤1.6 |
||||||
Nominal Discharge Current In(8/μ 20μ s)KA |
2 |
5 |
10 |
20 |
20 |
30 |
Maximum Discharge Current Imax(8/μ 20μ s)KA |
8 |
10 |
40 |
85 |
||
Response Time ns |
<25 |
|||||
Test Standard |
GB18802.1,IEC61643-1 |
|||||
The Cross Section of L/N line |
6 |
10 |
16 |
|||
The Cross Section of P/E line |
10 |
16 |
25 |
|||
Fuse or Switch(A) |
10A |
16A,32A |
16A |
|||
Operating Environment(℃) |
-40℃~+85℃ |
|||||
Relative Humidity |
≤95% |
|||||
Installation |
Standard Rail 35mm |
|||||
Material of Outer Covering |
Fiber glass reinforced plastic |